A 2-m 1.5-m section of wall of an industrial furnace burning natural gas is not insulated, and the temperature at the outer surface of this section is measured to be 80°C. The temperature of the furnace room is 30°C, and the combined convection and radiation heat transfer coefficient at the surface of the outer furnace is 10 W/m2 · °C. It is proposed to insulate this section of the furnace wall with glass wool insulation (k = 0.038 W/m · °C) in order to reduce the heat loss by 90 percent. Assuming the outer surface temperature of the metal section still remains at about 80°C, determine the thickness of the insulation that needs to be used. (answer : L = 3.4 cm)